yDO!BOOKEƒy[ƒWƒŠƒ“ƒNz fi-01@@@62 / 226 10•bŒã‚ÉBOOK‚̃y[ƒW‚Ɉړ®‚µ‚Ü‚· |
|
Azbil Corporation No. SS2-GTX00G-0200 - 3 - IECEx Intrinsic safety and Dust Certifications (Code E2) IECEx KEM 07.0058X Zone 0 Ex ia IIC T4 TPROCESS = 105 ‹C -30 ‹C < Tamb < +60 ‹C IP66 / 67 ELECTRICAL PARAMETERS: Ui = 30 V, Ii = 93 mA, Pi = 1 W, Ci = 5 nF, Li = 0.5 mH Ex iaD 20 IP66 / 67 T105 TPROCESS = 105 ‹C -30 ‹C < Tamb < +60 ‹C IECEx Type n and Dust Certifications (Code E5) IECEx KEM 07.0058X Ex nL IIC T4 TPROCESS = 105 ‹C -30 ‹C < Tamb < +60 ‹C IP66 / 67 ELECTRICAL PARAMETERS: Ui = 30 V, Ci = 5 nF, Li = 0.5 mH Ex tD A21 IP66 / 67 T85 TPROCESS = 85 ‹C -30 ‹C < Tamb < +75 ‹C Ex tD A21 IP66 / 67 T100 TPROCESS = 100 ‹C -30 ‹C < Tamb < +80 ‹C Ex tD A21 IP66 / 67 T110 TPROCESS = 110 ‹C -30 ‹C < Tamb < +80 ‹C KOSHA Flameproof (Code K1) Ex d II C T6 Tprocess = 85 ‹C -30 ‹C < Tamb < +75 ‹C Ex d II C T5 Tprocess = 100 ‹C -30 ‹C < Tamb < +80 ‹C Ex d II C T4 Tprocess = 110 ‹C -30 ‹C < Tamb < +80 ‹C EMC Conformity 89/336/EEC, 92/31/EEC, 93/68/EEC Electromagnetic Compatibility (EMC) Directive Measuring span / Setting range / Working pressure range Figure 1 Working pressure and temperature of wetted parts section (for general purpose models) Figure 2 Working pressure and temperature of wetted parts section (for oxygen and chlorine service) Supply voltage and load resistance 17.9 to 42 V DC. Reverse polarity protection is standard. A load resistance of 250 ƒ¶ or more is necessary between loops. See Figure 3. Figure 3 Supply voltage vs. load resistance characteristics Note) For communication with HART communicator or Comm- Pad, a load resistance of 250 ƒ¶ or more is necessary. Output Analog output (4 to 20 mA DC) with DE protocol Analog output (4 to 20 mA DC) with HART protocol Digital output (DE protocol) Model Measuring Span Measuring range Overload Resistance value GTX 60G 17.5 to 3500 kPa {0.175 to 35 kgf/cm2} -100 to 3500 kPa {-1 to 35 kgf/cm2} 5250 kPa {52.5 kgf/cm2} GTX 71G 0.7 to 14 MPa {7 to 140 kgf/cm2} -0.1 to 14 MPa {-1 to 140 kgf/cm2} 21 MPa {210 kgf/cm2} Temperature of wetted parts (¢ªC) Normal operating range Operative limit 101.3 {760} 100 6.67 2 {1.5} 0 40 6370 9.6 21.1 85 115 Working pressure P kPa {mmHg} Operative limit Temperature of wetted parts (¢ªC) Normal operating range Operative limit 101.3 {760} 53 {400} 0 40 70 80 Working pressure P kPa {mmHg} Operative limit 1345 1482 Load resistance (ƒ¶) Supply voltage - 12.5 0.0219 245 0 17.9 42 45 Load resistance (ƒ¶) Supply voltage (V DC) Operating Range = Operative limit 12.5 1 4 |