No. SS2-GTX00F-0100 Azbil Corporation - 6 - Handling precautions for HART specification devices . If you need to operate with a secondary host (HART communicator, etc.), set the communication interval of the primary host (DCS, device management system) to 8 seconds or more, or suspend communication from the primary host. If the primary host repeats HART communication within 8 seconds, the request from the secondary host may not be received (communication may not be possible). . If electrical noise in the environment prevents HARTcommunications with the host, take countermeasures such as separating the signal cables from the source of the noise, improving the grounding, changing to shielded signal cables, etc. Even if noise interferes with HART communications, the 4-20 mA analog signal will be unaffected and can be used for control. . If this product is being operated in multidrop mode, there is a limit to the number of devices that can be used. If you are using multidrop mode, please consult with us. PERFORMANCE SPECIFICATIONS Max working pressure Note) 1. Max. working pressure depends on flange rating, flange materials and operating temperature. Please refer to the following data. Operating range of temperature depends on specification of transmitters. Note) 2. In case of flange type (GTX60F) and remote sealed type (GTX60U), max working pressure depends on the smaller value of either 1.5 MPa or following data. Note) 3. In case of remote sealed type (GTX71U), max working pressure depends on the smaller value of either 10 MPa or following data. JIS JPI/ANSI 304 SST 316 SST 316L SST 12.0 10.0 8.0 6.0 4.0 2.0 0.0 Max. Working Pressure (MPa) 63K 40K 30K 20K 10K 12.0 10.0 8.0 6.0 4.0 2.0 0.0 Max. Working Pressure (MPa) 600# 300# 150# 12.0 10.0 8.0 6.0 4.0 2.0 0.0 Max. Working Pressure (MPa) 63K 40K 30K 20K 10K 12.0 10.0 8.0 6.0 4.0 2.0 0.0 Max. Working Pressure (MPa) 600# 300# 150# 12.0 10.0 8.0 6.0 4.0 2.0 0.0 Max. Working Pressure (MPa) 63K 40K 30K 20K 10K 12.0 10.0 8.0 6.0 4.0 2.0 0.0 Max. Working Pressure (MPa) 600# 300# 150# |