No. SS2-KFP100-0100 - 2 - SPECIFICATIONS Standard Specifications Item Specification Detector Section Measuring range SUS316 bellows; 0 to 50, 0 to 100, 0 to 150, 0 to 200 kPa {0 to 0.5, 0 to 1, 0 to 1.5, 0 to 2 kgf/cm2} gauge pressure SUS316 spiral; 0 to 300, 0 to 400, 0 to 500, 0 to 600, 0 to 1000 kPa {0 to 3, 0 to 4, 0 to 5, 0 to 6, 0 to 10 kgf/cm2} 0 to 1.5, 0 to 2, 0 to 2.5, 0 to 3.5, 0 to 5 MPa {0 to 15, 0 to 20, 0 to 25, 0 to 35, 0 to 50 kgf.cm2} 0 to 7, 0 to 10, 0 to 15, 0 to 25, 0 to 35 MPa {0 to 70, 0 to 100, 0 to 150, 0 to 250, 0 to 350 kgf/cm2} gauge pressure Phosphor bronze bellows; 20 to 100 kPa {0.2 to 1.0 kgf/cm2} pneumatic pressure signal SUS316 bellows; -101.3 to 0 kPa { -760 to 0 mmHg} negative pressure Allowable over to range without recalibration Span of 7 MPa {70 kfg/cm2} or less; Maximum pressure plus 50% of span Span of 10 MPa {100 kgf/cm2} or more; Maximum pressure plus 20% of span Process connection G. internal thread Function Accuracy .. 1% FS (.. 1.5% FS for range of 0 to 15 MPa {0 to 150 kgf/cm2} or more.) Repeatability Within 0.3% Fs (within 0.45% FS for range of 0 to 15 MPa {0 to 150 kgf/cm2} or more.) Dead band Within 0.2% FS (within 0.3% FS for range of 0 to 15 MPa {0 to 150 kgf/cm2} or more.) Indication Angle 44 degrees Scale length 150mm Pointer Process variable ; Red, Set to point value ; Green Output indicator (.. 40 mm) Scale range; 0 to 200 kPa {0 to 2 kgf/cm2}, Indicator accuracy; .. 3% FS Set to point Section Local Setting Internal or external by setting knob Remote setting Pneumatic pressure setting of 20 to 100 kPa {0.2 to 1.0 kgf/cm2} Setting range 0 to 100% FS Controller Control action P + Manual reset, PI, PID, PD +Manual reset, PI + Batch, On to Off, Differential gap, P + External reset, PD + External reset Proportional band (P) 5 to 500% (direct or reverse action) Integral (I ) 0.05 to 30 min. Derivative (D) 0.05 to 30 min. Differential gap 1 to 100% FS, adjustable Batch setting pressure 60 to 110 kPa {0.6 to 1.1 kgf/cm2}, adjustable External reset pressure 20 to 100 kPa {0.2 to 1.0 kgf/cm2} Manual reset 0 to 100% FS, adjustable (by pneumatic pressure setting.) General Specifications Output 20 to 100 kPa {0.2 to 1.0 kgf/cm2}, 0 or Corresponding to supply air pressure (on to off, differential gap) Minimum load I.D. 4 mm .. 3 m + 20 cm3 Supply air pressure 140 .. 14 kPa {1.4 .. 0.14 kgf/cm2} Air consumption (50% output balanced) Indicating transmitter (A0) ; 4 L/min [N] Indicating controller (A1, A3) ; 4 L/min [N] Indicating transmitting controlling (A2, A4) ; 8 L/min [N] Manual controller (M) ; 3 L/min [N] Saturated air supply capacity Transmitter output ; 40 L/min [N] Controller output ; 40 L/min [N] Manual control output ; 30 L/min [N] Air connection Rc. or . NPT internal thread Ambient temperature 30 to 80..C Relative humidity 10 to 90% RH Case, Door Enclosure ; Rain to tight and dust to tight, meets JIS F8001 Class 3 splash to proof, NEMA 3, IEC IP54 Vibration resistant ......................Lloyd regulation or equivalent Materials ; Case ..........................................Aluminum die to cast Door ...........................................Polyester with fiberglass Door .glass................................Reinforced glass (3 mm thick) Case finish ; Acryl baking finish (for corrosion to resistant and silver finish, refer to the optional specification.) Color of finish ; Dark beige (munsell 10YR 4.7 / 0.5) Mounting Panel, wall or 2 to inch pipe mounting (mounting bolt, nut material; SUS304) Weight Approx. 5.8 kg (local model PI controller using 0 to 294 kPa {0 to 3 kgf/cm2} element without option.) |