No. SS2-KFD100-0100 -4 - Standard Specification (Continued) Item Specification Function Note) *1 ; When with elevation or suppression. Repeatability Within 0.3% FS Dead Band Within 0.2% FS Indication Angle 44 degrees Scale length 150 mm Pointer Process variable ; Red, Setpoint value ; Green Output indicator (40 mm) Scale range ; 0 to 200 kPa {0 to 2 kgf/cm2} Indicator accuracy ; .. 3% FS Set-point Section Local setting Internal or external setting by setting knob. Remote setting Pneumatic pressure setting of 20 to 100 kPa {0.2 to 1.0 kgf/cm2} Setting range 0 to 100% FS Controller Control action P+ Manual reset, PI, PID, PD + Manual reset, PI + Batch, On-Off, Differential gap, P+ External reset, PD, + External reset Proportional band (P) 5 - 500% (direct or reverse action) Integral (I) 0.05 to 30 min. Derivative (D) 0.05 to 30 min. Differential gap 1 to 100% FS, adjustable Batch setting pressure 60 to 110 kPa { 0.6 - 1.1 kgf /cm2} , adjustable External reset pressure 20 to 100 kPa { 0.2 - 1.0 kgf /cm2} , adjustable Manual reset 0 to 100% FS, adjustable (by pneumatic pressure setting) General Specification Output 20 to 100 kPa {0.2 to 1.0 kgf /cm2} , 0 or Corresponding to supply air pressure (on-off, differential gap) Minimum load I.D. 4 mm x 3 m + 20 cm3 Supply air pressure 140 .. 14 kPa {1.4 .. 0.14 kgf/cm2} Air consumption Indicating transmitter (A0) ; 5 L/min [N] (50% output balanced) Indicating controller (A1, A3) ; 9 L/min [N] Indicating transmitting controller (A2, A4) ; 9 L/min [N] Manual controller (M) ; 3 L/min [N] Saturated air supply capacity Transmitter output ; 40 L/min [N] Controller output ; 40 L/min [N] Manual controller output ; 30 L/min [N] Air connection Rc . or . NPT internal thread Ambient temperature At meter body (process fluid) ; -40 to +120 ..C (PVC cover; 0 to 55 ..C) At transmitter (ambient) ; -30 to +80 ..C Relative humidity 10 to 90% RH Case, Door Enclosure ; Rain-tight and dust-tight, meets JIS F 8001 class 3 splash-proof, NEMA 3, IEC IP 54 Materials ; Case……………………. Aluminum die-case Door…………………….. Polyester with fiberglass Door glass……………… Reinforced glass (3 mm thick) Case finish ; Acryl baking finish (for corrosion-resistant and silver finish, refer to the optional specification) Mounting Panel, 2 in. pipe or flange mounting. Weight 11.8 kg (when model KFDB12-221122A1P-X) Model no. Measuring range kPa ( mmH2O) Accuracy KFDB.... 11 0 - 25 to 0-less than 50 {0-2,500 to 0-less than 5,000} 0 - 50 to 0 - 500 {0 - 5,000 to 0 - 50,000} KFDB.... 22 0 - 2.5 to 0-less than 5 {0-250 to 0-less than 500} 0 - 5 to 0 - 53.9 {0 - 500 to 0 - 5,5000} Transmitting / Indicating .. 0.75 / ..1.0 (..1.25) % FS*1 .. 0.5 / .. 1.0 % FS KFDB.... 33 0 - 0.5 to 0-less than 1 {0-50 to 0-less than 100} 0 - 1 to 0 - 6 {0 - 100 to 0 - 600} KFDB.... 44 0 - 0.1 to 0-less than 0.2 {0-10 to 0-less than 20} 0 - 0.2 to 0 - 0.2 {0 - 20 to 0 - 20} KFDB.... 61, 71, 81 0 - 25 to 0-less than 50 {0-2,500 to 0-less than 5,000} 0 - 50 to 0 - 500 {0 - 5,000 to 0 - 50,000} KFDB.... 62, 72, 82 0 - 2.5 to 0-less than 5 {0-250 to 0-less than 500} 0 - 5 to 0 - 53.9 {0 - 500 to 0 - 5,5000} Transmitting / Indicating .. 1.0% FS / ..1.5 % FS .. 0.5% FS / .. 1.0% FS |