【DO!BOOK・ページリンク】 fi-06 30 / 46 10秒後にBOOKのページに移動します |
|
No. SS2-KFD100-0100 -5 - Item Specifications (1) External SP setting knob (for local setting) A setting knob is mounted on the door. SP can be adjusted from outside. (2) Built-in manual controller (with auto-manual transfer switch) Consist of manual control regulator, two position transfer switch and balance check button. (3) With manifold valve (except type 6.. / 7.. detector) Manifold valve Direct Mounting type High pressure type KFD Without Extension type With Extension type NZ16 KFDB.... -11 .. " -22 .. " -33 .. " -44 .. .. " -81 .. " -82 .. (4) Elevation , Suppression Elevation ; The lower limit of input range is above zero. Suppression ; The lower limit of input range is below zero. (5) Pressure regulator with filter (hot applicable to panel mounting type) Pressure regulator with filter plus 40 mm pressure gauge. (supply pressure ; 200 to 970 kPa {2 to 9.9 kgf/cm2}, output; 140 kPa {1.4 kgf/cm2} , pressure gauge; 0 to 200 kPa {0 to 2 kgf/cm2}) (6) High accuracy type (applicable model KFDB....-11-22) Note) *1: When with elevation or suppression. Model no. Measuring span kPa{mmH2O} Accuracy KFDB.... -11 50 to less than 500 {5,000 to less than 50,000} ..0.25 (..0.375)*1 KFDB.... -22 5 to less than 53.9 {500 to less than 5,500} KFDB.... -11 25 to less than 50 {2,500 to less than 5,000} ..0.5 (..0.75)*1 KFDB.... -22 2.5 to less than 5 {250 to less than 500} 6 4 |