No. SS2-KFL100-0100 Azbil Corporation - 2 - STANDARD SPECIFICATIONS Range of standard measuring setting range Specific-gravity 1. Use as level instrument, 0.1 to 1.6 in specific gravity. 2. Use as boundary surface are as following. If the specific gravity of upper layer liquid is γ2, the lower layer liquid one is γ3, it becomes γ2<γ3, 0.4<γ2, γ3<1.6, and 0.1<γ3-γ2<1.2 Please refer to Figure 1. Figure 1 Specific-gravity (0.1 to 1.6) Medium specific gravity: It is possible to correspond to JIS 63K or ANSI / JPI 600 as standard. Low specific gravity: It is possible to correspond to JIS 30K or ANSI / JPI 300 as standard. Please consult to our sales, except for the above-mentioned. Please refer to Table 1 for details. Working pressure range It is possible to use from -101.3 kPa up to each flange pressure rating. (Maximum JIS63K or ANSI/JPI600#), for ANSI/JPI900# is also available with some condition. Process connection Flange connections External chamber type Connection Side-side flanged, SIde-bottom flanged, Top-side flanged, Top-bottom flanged Flange size 2 inches or 1. inch RF, 2 inches or 1. inch RTJ (for ANSI / JPI 600#) Internal float type Connection Top flanged Flange size 3 inches RF, 4 inches RF, 5 inches RF, 3 inches or 1. inch RTJ (for ANSI / JPI 600#) Materials Refer to “Table 2 Material” on page 3 Meter specification Refer to “Table 3 Meter specification” on page 3 Mounting Direct mount to the process with flanges Weight Approx. 45 kg. Range (mm) Range of measuring setting range (mm) 0 - 300 Set applicable within left side range. 0 - 350 0 - 400 0 - 450 0 - 500 0 - 600 0 - 700 0 - 800 0 - 1000 0 - 1200 0 - 1500 0 - 2000 300 500 700 2000 1.6 0.6 0.4 0.2 0.15 0.1 Max range (mm) Medium Low Medium Low Medium Low Sp. Gr. Table 1 Float test pressure (Material: SUS316L) Model Measuring range (mm) Medium specific gravity (KFLB_ - 61) Low specific gravity (KFLB_ - 62) Float diameter (mm) Over load pressure (MPa) Flange pressure rating float diameter Float diameter (mm) Over load pressure (MPa) Flange pressure rating float diameter 03 0-300 55 15.0 Max. JIS63K, ANSI/JPI600 95 7.8 Max. JIS30K, ANSI/JPI300 A3 0-350 04 0-400 A4 0-450 05 0-500 06 0-600 45 85 3.2 Max. JIS10K, ANSI/JPI150 07 0-700 08 0-800 10 0-1000 12 0-1200 30 65 15 0-1500 20 0-2000 55 Float weight: 3 kg (Medium specific gravity type) (The weight difference depending on the specific gravity in case of the medium specific gravity type and the low specific gravity type in boundary surface meter as the specific gravity measurement type.) |