No. SS2-KFL100-0100 Azbil Corporation - 4 - PERFORMANCE Standard characteristic (within the range of specific gravity in Figure 1, under standard operating condition) Transmission accuracy : ± 0.5% F.S. Indication accuracy : ± 1.0% F.S. Repeatability : 0.3% F.S. Dead Band : ± 0.1% F.S. Optional specifications Internal manual loader (with auto/manual transfer switch) Consists of a manual control regulator, a two-position transfer switch and a balance check button. With external manual SP setting knob A setting knob is mounted on the door. SP can be adjusted externally. Water and oil free treatment (Only the SUS material) Range 1000 mm or less Remove the moisture and the oil from the wetted part. Oil free treatment (Only the SUS material) Range 1000 mm or less Remove the oil from the wetted part. Test report The result of visual checks and input output characteristics etc. for test (three points) of the level instrument is described and submitted. Five point check The measuring point of input output characteristics described to the test report is changed from 3 points (0, 50, 100%) to 5 points (0, 25, 50, 75, 100%). Mil sheet Test result of the chemical composition, the heat treatment condition, and the mechanical property of the element material (torque tube housing, bonnet, and chamber) with charge number of material is submitted. With air set Regulator with the filter + φ 40 pressure gauge is supplied. (Supply pressure; 200 to 970 kPa, output 140 kPa and pressure gauge; 0 to 200 kPa) Dye check The result of testing for the penetrant inspection in the weld of the element material (bonnet and chamber) is submitted. Without Float The float is not supplied. Please specify if the existing float of our company KQP..1.., or KFL..00 - ..1, or NQP31.. or NQP21.. is reused. Without chamber The chamber is not supplied. Please specify if the existing chamber of our company KQP..1.., or KFL..00 - ..1, or NQP31.. or NQP21.. is reused. Optional semi-standard and special specifications Stainless steel bolts (Y131) SUS304 bolts are used for the main body assembling. The connection standard based on High-pressure gas regulation goods with JIS10K, ANSI150, and JPI150 it becomes a special requirement. Please consult to our sales. Corrosion-prevention and silver painting (Y138) Prevent corrosion (acrylic baking) finishing (Y138A) Resistant against corrosive atmosphere Preventive corrosion resistant (epoxy baking) finishing (Y138B) Resistant against corrosive liquid. Silver general (acrylic baking) finish (Y138C) Resistant of heating up of equipment by direct sunshine or radiant heat. Silver preventive corrosion (acrylic baking) finishing (Y138D) Protection of heating up of equipment and corrosive atmosphere. Note) The silver finishing is not suitable for alkaline atmosphere. Table 4 Operating temperature range (°C) Standard operating range Normal operating range Limit operating range Transportat ion storing range Ambient temperature 23 ±2 -30 to +80 -40 to +85 -40 to +85 Liquid temperature 23 ±2 -196 to +400 -196 to +400 -40 to +85 (Other materials: U, M) (Other materials: A, E, D) With radiation fin Without radiation fin (Other materials: U, M) (Other materials: A, E, D) With radiation fin Without radiation fin Liquid temperature ( C) Ambient temperature ( C) Liquid temperature ( C) Ambient temperature ( C) (-30, -30) (-30, -30) (0, -196) (0, -196) Level measurement except for boiler Level measurement for boiler and boundary surface measurement |