No. SS2-PCA100-0100 - 3 - Power Consumption Approx. 5 VA Insulation Resistance 500 V DC, 100 M.. or greater Dielectric strength Between input terminals and relay terminals 1000 V AC, 1 min. Between input terminals, relay terminals and outer box 1500 V AC, 1 min. Between power supply terminals and relay terminals 1500 V AC, 1 min. Between power supply terminals and ground, outer box 2100 V AC, 1 min. Between input terminals and analog output terminals 500 V AC, 1 min. Accessories Unit seal Shipment data setting when ex-factory Comparison Setting SW NO. Range Scaling or Output setting AL1 AL2 Hysteresis Output Detay Display Frequency 0 . . . . . . . 1 Pt100 0.0~500.0 2 R 0~1000 3 K 0~1000 4 J 0~500 5 T 0~200 6 B 0~1000 7 Pt100 32.0~932.0 8 R 32~1832 9 K 32~1832 A J 32~932 B T 32~392 C B 32~1832 D Input to receiver 0~4000 OFF OFF 1 0 F (400 ms) E Loop check 0 . . . . . F . . . . . . . 8 3