【DO!BOOK・ページリンク】 fi-08 23 / 26 10秒後にBOOKのページに移動します |
|
No. SS2-PCM100-0100 - 2 - SPECIFICATIONS Input 4 to 20 mA DC, 1 to 5 V DC Open collector, Non-voltage contact pulse (contact capacity: 12 V DC, 10 mA), Voltage pulse (4.5 to 30 V on H level, 0 to 2.0 V on L level) Pulse frequency 100 Hz or 1000 Hz max. Pulse width 5 ms or more at 100 Hz 0.3 ms or more at 1000 Hz Duty ratio 50% or less Output 4 to 20 mA DC, Open collector pulse (10, 500, 1000 Hz, output capacity: 30 V DC, 200 mA max.) Contacts (process value: 2 contacts, totalized value: 2 contacts, contact capacity: 250 V AC, 0.3 A) Distributor function 12 V DC ±5% / 150 mA max. 24 V DC ±5% / 50 mA max. Reset function Resets totalized count and totalized initial value (using front mask internal switch or external reset signal). Power supply 90 to 264 V AC, 50/60 Hz, 24 V DC ±10% Display Green or red LEDs, Character height 15 mm Process value (5-digit) or totalized value (6-digit) Cut-off function 0 to 10% Ambient temperature range 0 to 50 °C Ambient humidity range 10 to 85% RH (no condensation) Storage temperature range -20 to 70 °C Case material ABS resin Memory Non-volatile memory, 10-year storage period Mounting Panel mounted with dedicated mounting bracket Mass Approx. 500 g Power consumption Approx. 16 VA Attachments Engineering unit seals (Pa, kPa, MPa, N/m2, bar, m3/s, m3/min, m3/h, Nm3/s, Nm3/min, Nm3/h, l/s, l/min, l/h, kl/min, Nl/min, Nl/h, W/h, kW/h, cal/h, kcal/h, Mcal/h, Gcal/h, T/h, t/h, g/h, m/s, A, m3, Nm3, l, kl, Nl, Nkl, W, kW, W-s, W-h, kW-h, cal, kcal, Mcal, Gcal, T, t, kg, g, m, km, Ah, kA..h) Setting at shipment Default value set at factory |